JOAP: SANHUA - R290 Propane Catalogue - 2020
63 sanhuaeurope.com SBV/SBV-R SERIES The ball valve of series SBV/SBV-R is applicable for commercial air conditioner, freezing or deep-freezing equipment or other refrigeration circuits in order to open and to shut off inner flow path by operating the valve stem. It can also be used as service valve for vacuum pumping and refrigerant injection etc. All the Ball Valves listed in this datasheet can be installed in system using flammable refrigerants HFO (categories A2* and A2L*), and Hydrocarbons HC (category A3*). *according ANSI-ASHRAE 34-2016 and EN-378-1 ANNEX EN 378-1:2016 Annex E FEATURES • STRAIGHTWAY TYPE, FULL PORT, LOWPRESSUREDROPS, COST-EFFECTIVE • VALVE BODYANDVALVE SEATWITHWELDEDSTRUCTURE,WITHHIGHPRODUCTRELIABILITY • ROTATE 1/4 CIRCLES FROMFULL-OPENTOFULL-CLOSE, EASY TOOPERATE • BIDIRECTIONAL FLOW • ROTATIONSTOPONREQUEST FORFULL-OPENAND FULL-CLOSEOF THEVALVE • SPECIAL SEALINGMATERIALS TOPREVENT INTERNAL LEAKAGE • CERTIFIEDACCORDING PED CAT.II BY TUVRHEINLAND BALL VALVE Note: 1) SBV: Peak temperature of +150°C for short term use 2) SBV-R: Peak temperature of +135°C for short term use GENERAL SPECIFICATIONS • Applicable for all common HCFC, HFC and HFO refrigerants such as: R22, R134a, R404A, R407A/ C/F, R410A, R507A, R448A, R449A, R450A, R452A, R513A, R32, R1234yf, R1234ze, R454A/B/C, R455A, R290, R1270, R600a • Medium temperature TS min./max.: -40°C / +120°C • Max. operating pressure PS: 4,5 (45bar) or 4,9 MPa (49 bar) depending by the model • Installation position: liquid, suction and discharge line in all directions • PED declaration • Certifications: UL/CUL available only for models with size until SBV07. For bigger sizes on request
Made with FlippingBook