>>> sanhuaclimate.com 159 SANHUA PRODUCTCATALOGUE DSG SERIES Liquid line Filter Drier withSight Glass SELECTION FORMULAS Filter Driers for liquid line are manufactured in compliance with ARI Standard 710. Maximum flow rate of liquid refrigerant at a differential pressure of 0,07bar (1psi) is indicated by kW (ton) which is based on the temperature of liquid refrigerant 30°C (86°F), the evaporating temperature of -15°C (5°F) and the following mass flow: • 0,40 kg/min/kW (3.1 lb/min/ton) R134a • 0,53 kg/min/kW (4.1 lb/min/ton) R404A, R507A • 0,39 kg/min/kW (3.0 lb/min/ton) R22, R407C • 0,36 kg/min/kW (2.8 lb/min/ton) R410A Note: Data on water absorption is based on the following EPD (method: ASHRAE Standard 63.1): • 60ppm R22 • 50ppm R134a • 50ppm R404A • 50ppm R407C • 50ppm R410A • 50ppm R507A Moisture Indication Limits Refrigerant Moisture Content 25°C: PPM Green/Dry Middle Color Yellow/Wet R22 <100 100~200 >200 R134a <90 90~180 >180 R404A <40 40~100 >100 R410A <90 90~300 >300 R507 <15 15~90 >90 R407C <120 120~280 >280 Refrigerant Moisture Content 40°C: PPM Green/Dry Middle Color Yellow/Wet R22 <140 140~350 >350 R134a <120 120~330 >335 R404A <80 80~160 >160 R410A <200 200~580 >580 R507 <80 80~170 >170 R407C <100 100~260 >260