SANHUA PRODUCTCATALOGUE STGB/F SERIES Bi-Flow Filter Driers SELECTION FORMULAS Filter driers for liquid line are manufactured in compliance with ARI Standard 710. Maximum flow rate of liquid refrigerant at a differential pressure of 0,07bar (1psi) is indicated by kW (ton) which is based on the temperature of liquid refrigerant 30°C (86°F), the evaporating temperature of -15°C (5°F) and the following mass flow: • 0,40 kg/min/kW (3.1 lb/min/ton) R134a • 0,53 kg/min/kW (4.1 lb/min/ton) R404A, R507A • 0,39 kg/min/kW (3.0 lb/min/ton) R22, R407C • 0,36 kg/min/kW (2.8 lb/min/ton) R410A Note: Data on water absorption is based on the following EPD (method: ASHRAE Standard 63.1): • 60ppm R22 • 50ppm R134a • 50ppm R404A • 50ppm R407C • 50ppm R410A • 50ppm R507A