R 410 A Rollkolbenkompressoren - Rotary Compressors ASG80CV ASG108CV ASH218SV ASH264SV Abb. 1 Abb. 2 Abb. 3 Abb. 4 Modell Kälteleistung Leistungs aufnahme Hub- volumen COP Betriebs kondensator Run Capacitor Höhe H Wicht Ø Gewicht Abb Model Capacity Power Consump- tion Displace- ment Height H Weight Ref. Btu Watt Watt Cm3 W/W M Fd/V mm mm kg 2 2 0 - 2 4 0 V - 1 - 5 0 H z ASG080CV* 6278 1840 679 8,0 2,71 30mF/400V 247,0 119,2 11,0 1 ASG108CV* 8701 2550 920 10,8 2,77 35mF/400V 247,0 119,2 11,0 1 ASL145SV 11489 3370 1160 14,0 2,90 35mF/450V 279,0 129,1 10,5 2 ASL155SV 12617 3700 1275 15,5 2,90 35mF/450V 279,0 129,1 10,5 2 ASL180SV 14834 4350 1500 18,0 2.90 35mF/450V 279,0 129,1 12,0 2 ASH201SV 16436 4820 1690 20,1 2,85 60mF/400V 298,5 140,1 13,5 3 ASH218SV 17664 5180 1786 21,8 2,90 60mF/400V 298,5 140,1 14,0 3 ASH264SV 21517 6310 2214 26,4 2,85 50mF/400V 298,5 140,1 15,5 3 ATH280CV 23393 6860 2382 28,0 2,88 60mF/450V 358,0 140,1 22,5 4 ATH290CV 24310 7125 2457 29,0 2,90 60mF/450V 358,0 140,1 22,5 4 ATH325CV 26462 7760 2723 32,5 2,85 60mF/450V 358,0 140,1 22,8 4 Bemerkung / Note 1: Kompressoren werden ohne Betriebskondensator geliefert / Compressors are supplied without run capacitor Weiteres über den Lieferumfang entnehmen Sie bite auch Seite 10 / Accessories see also page 10 Bemerkung / Note 2: Leistungsdaten basieren auf / Capacity refered to to= +7,2°C / tc = +51.4°C Bemerkung / Note 3: Die Modelle mit * sind mit externem Motorschutz ausgestatet. Modelle ohne * besitzen einen internen Motorschutz. Models with * have the external overload. The other models do have an internal overload .