Diagram Page 9 of 11 APFC Coil Supply Voltage L3 L7 L4 L5 L6 1 2 3 4 5 = ModBus A 6 = Modbus B 7 = GND 8 = Supply in or out. Consult LS Control before using Also see seperate Modbus document for description a t www.lscontrol.dk 8 motor output Cable shield must be connected with clamp 1 = HW1 hardware stop 2 = HW2 hardware stop 3 = LSC1. (Consult LS Control before using) 4 = LSC2. (Consult LS Control before using) NOTE: All cables except for supply voltage must be shielded. LED Explanation L1 = Green run LED - Flashes when OK L2 = Red Fault LED - ON when Fault L3 = Yellow Fault Type LED - Flashes error number. L4 = Yellow ModBus Communication LED - flashes fast L5 = Yellow LED reserved for future use L6 = Yellow LED reserved for future use L7 = Red hardware stop LED - ON=Fault, Flashes=OK HW Stop switch The inverter is supplied with a hardware (HW) Stop switch function. This HW Stop function can be used with a switch (e.g. a pressure switch or a thermal switch). The switch must be connected between connector HW1 and HW2 and it must be closed for the inverter to run the motor. If the switch is open the inverter is stopped and it will not be able to restart until the supply voltage has been disconnected long enough for the inverter to come to a complete stand still. Note: Wires between connector and cable shield MUST be as short as possible . Motor cable should NOT cross or be placed together with other wires / cables. L2 L1